Padlockable knob for enclosure doors, adding a simple way to secure cabinets and enclosures on site. Available from Valen Power.

Secure enclosure doors with this black padlockable wing knob, supplied with a quarter-turn cam lock. It gives a simple way to lock electrical enclosures and cabinets on site using a standard padlock.

The knob is made from Zamak zinc alloy with a black coating, a steel cam and a rubber gasket. It suits battery enclosures and equipment cabinets at remote and unattended sites where basic security against tampering is needed.

Price

+GST

Qty

Padlockable Wing Knob suit Enclosure

Features

Applications

Specifications

SKUBE76124
Length49 mm
Width49 mm
Height25.5 mm
Box Quantity1

Downloads

Download Specification Sheet

Download Information Sheet

Related Products

Frequently Asked Questions

What ventilation does a battery room or enclosure need?

VRLA vents hydrogen under over-charge and high temperature; hydrogen is flammable above roughly 4% in air. Requirements sit in AS 2676 and AS 3011. A sealed IP-rated cabinet containing a battery bank with no designed…

Full answer: What ventilation does a battery room or enclosure need?

What does the cabinet thermal design need to achieve?

More than most people specify, and it usually matters more than the battery choice. Queensland TMR (MRTS213) requires: an IP-rated, double-skinned enclosure with ventilation slots thermostatically controlled fans and a heater white (N14) heat-reflective paint…

Full answer: What does the cabinet thermal design need to achieve?

How do I keep battery banks alive in extreme heat?

Fix the enclosure before the battery. VRLA loses roughly 50% of its life for every 10 °C sustained above 20 °C, and heat damage cannot be reversed. In order of effect: Measure the temperature inside…

Full answer: How do I keep battery banks alive in extreme heat?

How does temperature affect front terminal battery life in Australian conditions?

Temperature is the dominant variable in Australian industrial battery life, and it is under-modelled almost everywhere. The relationship. EUROBAT states that float operation above 20 °C reduces VRLA life expectancy by approximately 50% for every…

Full answer: How does temperature affect front terminal battery life in Australian conditions?

Will a front terminal battery fit my existing rack?

Check the dimensions, not the amp-hours. There is no standard defining front terminal battery case dimensions. It is a de facto industry convention shaped by rack depth and shelf pitch, not a standardised footprint, which…

Full answer: Will a front terminal battery fit my existing rack?