There are three likely causes, in order:
- The battery has lost capacity. End of life is usually 80% of rated, and a bank at 60% gives only a fraction of its original runtime.
- The load has grown since the bank was specified. This is very common in rooms that have had equipment added over the years.
- One weak battery is dragging the string down. In a series string, capacity is set by the weakest battery.
To diagnose it: measure the actual load first, then test the string, then test individual batteries.