Range

Warranty

ENDUROGEL

24 months

ENVIROX-CEL

24 months

ENVIROX-CELPLUS

24 months

TOPIN Front Terminal

24 months

ENLiFEN Front Terminal

36 months

Extended warranty is available on request.

You will notice the gap between warranty and design life, 24 months against a 15-year design life on ENDUROGEL, for example. That gap is normal across the industry rather than unique to Valen, and it exists because the two things measure different risks: warranty covers manufacturing defect, while design life describes expected performance under specified conditions.

Australian specifiers for critical infrastructure routinely require both and treat them separately. A typical specification might ask for a design life over ten years alongside a twelve-month warranty. They are answering different questions.

What actually decides a claim is the conditions, so read those rather than the headline period:

  • Ambient and cell temperature range the warranty assumes. This is where most claims fail. A long-design-life battery installed in a 45 °C cabinet has not failed prematurely in the manufacturer’s view. It has been operated outside the assumed conditions.
  • Float voltage and temperature-compensation regime, and whether your charger actually delivers it. A charger without temperature compensation may itself be the reason a claim is declined.
  • Evidence of a controlled charge regime. This is increasingly explicit in manufacturer warranty terms. Many manufacturers now require proof that the battery was operated within a controlled regime. Monitoring data is warranty evidence.
  • Depth of discharge limits, and for lithium, throughput or cycle caps and battery management system firmware currency.
  • Who bears freight and labour on a warranty replacement to a remote site. On a site four hours from a depot this can exceed the value of the battery.
  • What documentation is required at claim time: commissioning records, discharge test results, monitoring logs, service history.

 

The most useful thing you can do at installation is start the evidence file: commissioning readings, baseline impedance, and the temperature record. It costs an hour and it is the difference between a complaint and a case.

4. SOLiCORE 48V 100Ah Semi-Solid State LiFePOâ‚„ Rack Mount Battery

Page: https://valen.com.au/shop/lithium-batteries/valen-solicore-solid-state-lithium-batteries/valen-solicore-48v-100ah-solid-state-lifepo4-rack-mount-battery/ Questions: 17 · First six above the spec table URL stays as-is. No redirect required.

4.1 Two page edits required before the FAQ goes live

Edit 1, remove the following text from the product description:

“Solid‑State Safety: No liquid electrolyte, offering higher stability, no fire/smoke risk, and safer operation.”

Replace with:

“Semi-Solid State Safety: a composite polymer electrolyte with substantially reduced free liquid electrolyte, delivering higher thermal stability and improved abuse tolerance compared with a conventional lithium cell. Certified to IEC 62619, UN 38.3 and UL 1973, and tested to UL 9540A.”

Edit 2, replace “solid state” with “semi-solid state” in the visible body copy and headings on this page. The product name, the URL and the page slug stay unchanged; this is a body-copy change only. The FAQ below explains the distinction, which is deliberate. It is a credibility asset, not a concession.

4.2 Specification summary: please publish on the page

Parameter

Specification

SKU

48ELSS100

Nominal voltage

48 V system (51.2 V nominal)

Capacity

100 Ah, approximately 5.1 kWh

Chemistry

LiFePOâ‚„ with composite polymer (semi-solid) electrolyte

Form factor

3U, 19-inch rack mount

Dimensions

517 mm × 442 mm × 133.5 mm

Charge voltage

57.6 V ± 0.8 V (56.8–58.4 V)

Charge current

20 A standard, 50 A fast charge

Discharge current

100 A continuous, 250 A peak for 2 seconds

Discharge cut-off voltage

40 V

Charge temperature range

0 °C to 55 °C

Discharge temperature range

−20 °C to 60 °C

Storage temperature range

−20 °C to 45 °C

Low temperature performance

Over 97% of discharge capacity at −20 °C

Cycle life

5,000+ at 100% DoD · 10,000 at 80% DoD

Parallel configuration

Up to 16 units

Ingress protection

IP54 metal case

Communications

2 × RS485, 1 × CAN, LCD display

Certification

IEC 62619, UN 38.3, UL 1973. Tested to UL 9540A

Warranty

5 years

4.3 FAQ

Enquire Now

Login Required

An account is required to add products to your cart, please login or register for an account.