Parameter |
Rating |
|---|---|
|
Solar array |
8.16 kWp, foldable, gas-strut assisted frame |
|
Solar charge controllers |
8 MPPT trackers, 35 kW maximum charge power, 5 kW per tracker, 99.90% MPPT efficiency, 580 V maximum PV open-circuit voltage |
|
Battery |
43 kWh nominal / 41 kWh usable, LiFePOâ‚„, 48 V DC, built on Valen SOLiCORE modules |
|
Battery cycle life |
5,000+ cycles at 100% DoD · 10,000 cycles at 80% DoD |
|
Battery charge temperature |
0 °C to 55 °C |
|
Battery discharge temperature |
−20 °C to 60 °C |
|
Inverter |
30 kVA continuous at 25 °C, derating to 23.8 kVA at 40 °C |
|
AC output |
230/240 V, total harmonic distortion under 2%, 96% maximum efficiency |
|
Backup generator |
27 kVA, aluminium super-silent enclosure |
|
Fuel tank |
100 L, bunded, mounted in the trailer base for a low centre of gravity |
|
Surge (5 seconds, motor starting) |
200 A |
|
Short-term peak (1 minute) |
85 A |
|
Maximum demand (5 minutes) |
75 A |
|
Short circuit |
375 A |
Note the inverter derating, 30 kVA at 25 °C becomes 23.8 kVA at 40 °C. We publish it because it is real and because a 40 °C day is not unusual anywhere in Australia. Any mobile power system quoting a single inverter figure without a temperature is quoting the best case; ask for the derated figure at 40 °C before you size your load against it.
Runtime depends on load, solar yield and whether the generator is enabled. With the generator running as backup, runtime is limited by fuel rather than by battery, the 100 L tank governs. Solar-only runtime is a function of daily generation against daily consumption, which is a site and season calculation rather than a product specification. Model your own case with the V-Trail calculator, or send us the load and location and we will do it with you.