Vantara delivers 30 kVA of continuous inverter output per unit at 25 °C, standard and configurations available up to 90 kVA continuous. AC output is 230/240 V with total harmonic distortion under 2% and maximum efficiency of 96%.
Surge capability is usually the deciding specification, not continuous rating, and it is where most off-grid systems fail in service. Inductive loads, bore pumps, irrigation, compressors, workshop machinery, refrigeration, draw three to six times their running current at start.
Vantara’s connection capability:
|
Duration |
Capability |
|---|---|
|
Continuous, 1 hour |
115 A |
|
5 minutes |
135 A |
|
1 minute |
150 A |
|
5 seconds (motor starting) |
200 A |
|
Short circuit |
320 A peak |
That 200 A five-second surge is what lets a Vantara start a pump without oversizing the whole system to cover a two-second event. The alternative, specifying a system twice as large as the continuous load requires, is how off-grid projects end up with capital cost that kills the business case.
Tell us at design stage what the largest single motor on site is and whether it has soft-start. During initial system start-up, sequence the load bring-up in steps rather than applying all loads at once. This manages inrush current and protects the system from unnecessary stress at commissioning.