Yes, less than a flooded cell, but not none. VRLA batteries recombine most of the gas produced internally, which is why they are described as sealed and require no watering. But recombination is not perfect, and under over-charge, high temperature or fault conditions the pressure relief valves vent hydrogen. Hydrogen is flammable in air at concentrations above roughly 4%.
The requirements in Australia sit in AS 2676 for installation, maintenance and testing of secondary batteries in buildings, and AS 3011 for the electrical installation. Rail applications carry the same obligation, ARTC’s signalling power systems standard requires battery housing ventilation to comply with AS 2676.
What this means in practice:
- Enclosures need a designed air path, not just a gap. A sealed IP-rated cabinet with no ventilation provision and a battery bank inside it is a design error.
- Hydrogen accumulation is a function of charge regime and temperature, so a charger without temperature compensation increases the ventilation requirement as well as shortening battery life.
- Where a dedicated battery room is used, note that AS/NZS 5139 Amendment 1 (2025) introduced a formal definition, a garage or storeroom does not qualify.
If you are retrofitting a larger bank into an existing enclosure, the ventilation calculation should be revisited. It scales with the bank.