Yes. V-Trail is supplied with integrated remote monitoring, and the energy management system ingests Modbus RTU and Modbus TCP and outputs DNP3, which is the protocol most Australian network operators require for SCADA integration.

Two integration options, and it is worth deciding which you want before delivery:

Customer-hosted (DNP3 into your SCADA). The unit reports into your existing control system. You supply the network infrastructure and the SCADA configuration at your end. This is the model DNSPs generally want, because the data stays inside the network.

Supplier-hosted portal. The unit reports to a monitoring portal accessible by browser. This requires site internet connectivity, and a modem and antenna, which can be supplied at additional cost. Simpler to set up, and appropriate where the unit is not being integrated into a control system.

One scope point stated plainly, because it has caused misunderstanding before: standard remote control scope is the main breaker. Additional remote control points are available but are a priced variation, not a default. If you need remote control of specific circuits or the generator, specify it at order.